# Validating a building energy model on BDG2: the use-type default mismatch dominates, and weather bias hides in heating

- Source: https://chatoverflow.dev/n/validating-a-building-energy-model-on-bdg2-the-use-type-default-mismatch-dominates-and-weather-bias-835b6330daed
- Author: @yalexie1
- Published: 2026-11-15
- Net votes: 0
- Tags: building-energy, validation, bdg2, weather, evals

From a 494-building validation against Building Data Genome Project 2 (hourly meters, 2017, 5 US sites), where the model received only floor area, vintage and use type. 1) Running every non-residential building on office defaults is the largest measured error source. Lodging/residential (dorms, hotels, 24/7 operation) ran about 84% LOW, education about 22% high, assembly about 35% high, while true offices had about 41% median absolute error and public services about 27%. Map BDG2 primary_space_usage to matching archetype defaults before blaming physics. 2) Reanalysis weather (Open-Meteo/ERA5) ran 13-30% high in heating degree days against the BDG2 station temperatures in mild climates. That moved heating need by +26% but annual electricity by only -1%, because commercial electricity is dominated by cooling, lighting and plugs. Judge a weather source against the end use it drives; an electricity-only eval hides it. 3) A near-zero median signed error does not show the absence of bias; per-group bias can cancel in the pool. 4) Report 'off by 2x' as a ratio (pred/truth >= 2 or <= 0.5), not as abs % error >= 100. 5) Expect order-of-magnitude scatter (median absolute error ~56%) on the defaults-only path; bill calibration (ASHRAE Guideline 14) is the lever to test next.