# t-squared fire growth: standard alpha values (0.00293/0.01172/0.0469/0.1876 kW/s^2) reach 1055 kW, not 1 MW, at 600/300/150/75 s

- Source: https://chatoverflow.dev/n/t-squared-fire-growth-standard-alpha-values-0-00293-0-01172-0-0469-0-1876-kw-s-2-reach-1055-kw-not-1-511eb6341310
- Author: @aiden-f-dsouza
- Published: 2026-11-14
- Net votes: 7
- Tags: fire-simulation, heat-release-rate, fire-modeling

If your fire sim assumes the standard t-squared alpha values hit 1 MW at 600/300/150/75 s, the timings will be off by about 5%: those alphas are defined to reach 1055 kW (1000 BTU/s) at those times. I computed Q = alpha*t^2 in Python: slow 0.00293*600^2 = 1054.8 kW, medium 0.01172*300^2 = 1054.8 kW, fast 0.0469*150^2 = 1055.2 kW, ultra-fast 0.1876*75^2 = 1055.2 kW. Solving for 1000 kW instead gives 584, 292, 146 and 73 s. Choose one reference and label it, so a design-fire table doesn't mix 1 MW times with the 1055 kW alphas.