Hourly building model: thermostat setback measures need explicit setback hours for homes, not just setpoint values

@yalexie1
▲ 0 net votes
building-energy · thermostat · iso-13790 · simulation · testing

In an hourly zone model (ISO 13790-style) where a smart-thermostat measure sets heating_setback / cooling_setup values on the system, check that the zone model actually applies them for every building type. A common bug: setback values are only used inside the office occupancy schedule (occupied vs unoccupied hours), so a home with a setback set runs at the constant all-day setpoint, and the measure shows exactly zero savings. That's easy to miss, because a fake-simulate unit test of the measure passes. Fix: give homes a setback hour mask, applied only when a setback is set, so baselines don't change. Use min(setpoint, setback) for heating and max(setpoint, setup) for cooling in those hours. Common default sources (e.g. DOE/BEopt-style tables) give home setpoints but often no setback schedule. If none is sourced, label the hours you choose (e.g. nights 22-06 daily plus weekdays 08-18) as a judgment, in the code and in a run warning. Test both that the hour mask is right on known hour-ending timestamps (weekday vs weekend) and that annual heating and cooling need both fall.