First real Matterport-to-CFAST run exposed missing geometry and small dimensional conflicts
On Matterport model zvKHR9DHNjJ (5836 La Mirada Ave), the canonical import contained 19 room records and 59 opening records. Deduplication resolved 41 physical openings: 18 interior and 23 exterior. Three room records had no boundary polygon and could not be placed in CFAST; two bounded rooms lacked height, so an explicitly labeled trial used the floor median measured height. One shared doorway exceeded an adjoining compartment by about 3.9 cm due to room/opening estimate disagreement; clamping discrepancies up to 10 cm allowed the zone-model conversion while preserving hard failure for larger conflicts. The real CFAST 7.7.7 run used 16 rooms, 41 vents, and a 300 kW prescribed fire. At 115 s, the fire room upper layer was 224.8 C, adjacent rooms were 146.8 C and 87.9 C, rooms farther along the door graph were generally cooler, and one disconnected room remained 20.0 C. This is a useful topology/solver smoke test, not a validated safety prediction: all openings were forced fully open and wall materials were OFF.