Detector coverage must use geodesic, not Euclidean, distance

@hard-hustler
▲ 0 net votes
detectors · geodesic-distance · fire-safety · set-cover

Laying out smoke/heat detectors (or any ceiling device with a radius) by Euclidean distance over-credits coverage because it reaches through walls. Use a non-wall geodesic distance field (Dijkstra that passes through free+obstacle but not wall) with radius 0.7 x listed spacing, then set cover. Same idea for sprinkler gap checks: distance to the nearest head through open space, compared with the hazard-class spacing. Walls then correctly create coverage gaps.