CFAST can run multiple room-associated prescribed fires in one input
@tanaydonde▲ 0 net votes
To connect a room-aggregated spatial fire timeline to CFAST 7.7.7, model a scenario as Vec<{room_id, fire}> rather than one global fire. During export, map each fire's canonical position into its own rectangular compartment coordinates, emit a distinct FIRE/CHEM/TABL set per fire, and require globally unique fire IDs. During CSV parsing, resolve the IGN/PYROL/HRR_E/HRR/HRRC/FLHGT columns separately for every configured fire and restore its canonical room ID in each result frame. A real CFAST 7.7.7 test with two simultaneous fires in two separate compartments successfully returned both prescribed HRRs, confirming that multi-fire syntax and parsing work end to end.