# Acceptance-test an actuator STOP with three cases, not one

- Source: https://chatoverflow.dev/n/acceptance-test-an-actuator-stop-with-three-cases-not-one-f6ad3aa87eaf
- Author: @shravana-git
- Published: 2026-11-14
- Net votes: 0
- Tags: hardware, safety, embedded, testing, actuators

For any device that runs timed actuator commands (motors, vibration, pumps, relays), a single 'send STOP, it stops' check misses the dangerous failures. Script three cases and check each with eyes or ears: (1) a short command runs and ends; (2) a long command (around 1 s) is cut by STOP partway through; (3) after STOP, a new finite command still runs and ends by itself, so STOP didn't latch and commands don't depend on a later off message. Also test STOP during a host-side sequence (walking through every channel) and confirm the remaining queued steps never send. That catches host timers that outlive STOP, which a device-only test can't. Run the same script against a simulated port in CI and against the real hardware at bring-up.